Trane Conquest CGAX015 Air-cooled Scroll Chillers Cooling Only 146kW/146000Btu 415V~50Hz

Trane Conquest CGAX015 Air-cooled Scroll Chillers Cooling Only 146kW/146000Btu 415V~50Hz

£11,104.53 £9,253.78 (ex. VAT)
Stock Status: In Stock
Blog
Trane Conquest CGAX015 Air-cooled Scroll Chillers Cooling Only 146kW/146000Btu 415V~50Hz

Trane Conquest chillers, CGAX, air cooled scroll compressor type liquid chillers and CXAX heat pumps, are designed for outdoor installation. Units can have one or two independent refrigerant circuits, two or more compressors per circuit. Unit are packaged with an evaporator made with a braze plate heat exchanger, and one or more condenser coils. Each unit is completely assembled, hermetic package, refrigerant circuit factory piped, electrical components wired, leak tested, dehydrated, charged and tested for proper control operations prior to shipment. The chilled water inlet and outlet openings are covered for shipment. A new generation of chiller control systems, providing improved control capabilities. Integrated safety protocols to protect both compressor and motor from electrical faults like thermal overload and phase reversal.

Each refrigerant circuit is provided with filter, electronic expansion valve, and charging valves. In cooling mode on the CXAX or on the CGAX, the evaporator is a brazed plate and frame heat exchanger equipped with water drain and vent connections on the water piping. Condenser coil is available in four different configurations: fin and tube with aluminium fi ns, or black epoxy pre-coating aluminium fi ns for the heat pump versions, and Micro-Channel type or E-coating Micro-channel type for the cooling only versions.

R454b refrigerant chiller Trane

CGAX Cooling Only General Data:

CGAX 015 SE-SN

Net Cooling Capacity (1)

(kW)

43

Total Power input in cooling (1)

(kW)

15

Short Circuit Unit Capacity (9)                                    (kA)           12   

Power Cable Cross Section (max)

mm²

35

Disconnect switch size

(A)

80

Digit 12=2 or Digit 12=1 and Digit 41=2

Maximum Power input

(kW)

20.4

Unit rated amps

(A)

34.5

Unit start up amps (w/o soft starter - Digit 26=A) (4)

(A)

117.0

Unit start up amps (with soft starter - Digit 26=B) (4)

77.8

Power factor

0.868

Digit 12=1 and Digit 15=A

Maximum Power input

(kW)

19.4

Unit rated amps

(A)

33.8

Unit start up amps (w/o soft starter - Digit 26=A) (4)

(A)

116.3

Unit start up amps (with soft starter - Digit 26=B) (4)

77.1

Power factor

0.845

Digit 12=1 and Digit 15=C

Maximum Power input

(kW)

20.4

Unit rated amps

(A)

34.5

Unit start up amps (w/o soft starter - Digit 26=A) (4)

(A)

117.0

Unit start up amps (with soft starter - Digit 26=B) (4)

77.8

Power factor

0.868

Compressor Number per Circuit                                    #             2              

Type

Scroll

Model Circuit1 / Circuit 2

7,5+7,5

Max Compr Power input Circuit 1/Circuit 2

kW

9,2 + 9,2

Rated Amps Circuit1 / Circuit 2 (4)

(A)

15,5 + 15,5

Locked Rotor Amps Circuit1 / Circuit 2 (4)

(A)

98 + 98

Motor RPM

(rpm)

2900

Oil sump heater Circuit1 / Circuit 2

(W)

0,17 / 0

Evaporator model

P80x66

Evaporator Water Content volume

(l)

3.8

Nominal water connection size                                   (in) -

(Grooved coupling) - Without HYM                             (mm)     2" - 60,3

Nominal water connection size                                   (in) -

(Grooved coupling) - With HYM                                  (mm)     2" - 60,3

Hydraulic Module Components

Single pump - Standard head pressure option

Max available Head Pressure

(kPa)

96

Motor Power

(kW)

1.20

Rated Amps

(A)

2.44

Single pump - High head pressure option

Max available Head Pressure

(kPa)

170

Motor Power

(kW)

2.30

Rated Amps

(A)

5.03

Twin pump - Standard head pressure option

Max available Head Pressure

(kPa)

96

Motor Power

(kW)

1.20

Rated Amps

(A)

2.44

Twin pump - High head pressure option

Max available Head Pressure

(kPa)

170

Motor Power

(kW)

2.30

Rated Amps

(A)

5.03

Expansion Tank Volume

(l)

25

Max User water loop Volume for factory mounted expansion tank (1) (l)

1450

Optionnal water Buffer tank volume                              (l)

324

Antifreeze Heater without pump package                     (W)

120

Antifreeze Heater with pump package                          (W)

280

 

Condensing Unit Type: Full aluminium Micro channel heat exchanger

Quantity of coil

#

1

Face area per circuit

(m²)

2.23