Mitsubishi Heavy Industries Air Conditioning FDC71VNP-W + FDT71VH Cassette Inverter Heat Pump 7Kw/24000Btu A+ 240V~50Hz
This Kit Includes:
1 of Mitsubishi Heavy Industries Air Conditioning FDT71VH Cassette R32 7Kw
1 of Mitsubishi Heavy Industries Air Conditioning FDC71VNP-W Outdoor Unit R32 7Kw R32
1 of Mitsubishi Heavy Industries Air Conditioning Eco Touch RC-EX1A Wired Remote Controller 2 wire PAC

Cassette Heat Pumps for Commercial And Residential Applications. Ideal for large open plan areas, or irregular shaped rooms. High efficiency with low noise levels.
Mitsubishi Heavy Industries air conditioning has made a giant leap forward in air conditioning and heat pump technology with the development of the high performance standard cassette range. The Mitsubishi Heavy Industries air conditioning split cassette units are ideal for commercial application such as offices, shops, meeting rooms, restaurants, hotels, clubs, gyms, and open plan areas. The Advanced FDT Cassette range has now been extended to include new small capacity inverter heat pump systems starting at 4Kw, and an extra high capacity system 14Kw at the top end. The 7-Day Programmable Timer now included in standard controls specification.
The improved air flow pattern through the unit and the new design high performance heat exchanger have resulted in a pressure loss reduction, allowing the fan design to be optimised for significantly lower sound levels. The air discharge louver has been modified to minimise air smudging on the ceiling adjacent to the air outlets.
Product Key Feature's:
• 7-Day 24 HR Programmable Timer
• Two on/off settings each day
• Different temperature for each set period
• External timer/BMS switching for Group (up to 16 units)
• Wall Controller - hard wired
• Integral temperature sensor
• Slim 298mm Construction
• Infra-red wireless controller optional
• INVERTER technology
• Low profile attractive grey/white fascia panel
• Improved anti-smudge air discharge
• Low ambient control included
• Auto re-start after power interruption
• Reduced sound levels
• Long pipe-runs up to 30 Meters
• High C.O.P
• Integrated condensate pump
Technical Data:
Indoor unit
|
FDT71VH
|
Outdoor unit
|
FDC71VNP-W
|
Power source
|
1 Phase 220-240V, 50Hz / 220V, 60Hz
|
Nominal cooling capacity (Min~Max)
|
kW
|
7.1 ( 3.2 ~ 8.0 )
|
Nominal heating capacity (Min~Max)
|
kW
|
8.0 ( 3.6 ~ 9.0 )
|
Power consumption
|
Cooling/Heating
|
kW
|
1.96 / 1.91
|
EER/COP
|
Cooling/Heating
|
|
3.62 / 4.19
|
Inrush current
|
A
|
5
|
Max. running current
|
A
|
17
|
Sound power level*1
|
Indoor
|
Cooling/Heating
|
dB(A)
|
59 / 60
|
Outdoor
|
Cooling/Heating
|
66 / 66
|
Sound pressure level*1
|
Indoor
|
Cooling (Hi/Me/Lo/Ulo)
|
46 / 34 / 31 / 26
|
Heating (Hi/Me/Lo/Ulo)
|
46 / 34 / 31 / 26
|
Outdoor
|
Cooling/Heating
|
51 / 48
|
Air flow
|
Indoor
|
Cooling (Hi/Me/Lo/Ulo)
|
m3/min
|
28 / 18 / 15 / 12
|
Heating (Hi/Me/Lo/Ulo)
|
28 / 18 / 15 / 12
|
Outdoor
|
Cooling/Heating
|
60 / 50
|
Exterior Dimensions
|
Indoor
|
Height x Width x Depth
|
mm
|
Unit: 236 x 840 x 840 Panel: 35 x 950 x 950
|
Outdoor
|
750 x 880(+88) x 340
|
Net weight
|
Indoor / Outdoor
|
kg
|
26(Unit:21 Standard Panel:5) / 60
|
Refrigerant
|
Type/GWP
|
|
R410A/2088
|
Refrigerant
|
Charge
|
kg/TCO2Eq
|
2.95/6.160
|
Refrigerant piping size
|
Liquid/Gas
|
ø mm
|
9.52(3/8") / 15.88(5/8")
|
Refrigerant line (one way) length
|
m
|
Max. 50
|
Vertical height differences
|
Outdoor is higher/lower
|
m
|
Max.30 / Max.15
|
Outdoor operating temperature range
|
Cooling*2
|
°C
|
-15~43
|
Heating
|
-20~20
|
Panel
|
|
White: T-PSA-5BW-E, T-PSAE-5BW-E
|
Air filter quantity
|
Pocket plastic net x 1(Washable)
|
Remote control
|
Eco Touch RC-EX1A Wired Remote Controller 2 wire PAC
|
Energy Class (Cooling/Heating)
|
|
A+/A+
|
SEER
|
|
5.72
|
SCOP (Average climate)
|
|
4.34
|
Pdesign (cooling/heating(@-10°C))
|
kW
|
7.1/5.8
|
Annual Electricity Consumption (cooling/heating)
|
kWh/a
|
435/1873
|
Designated Heating Season
|
|
Average
|
PDF Data Sheet:
Page 24

These air conditioning units must be installed by an F-Gas qualified engineer. We can install the unit for you using our F-Gas Certified Engineers. Please note if you do not select our installation service we will not ship the unit until we have obtained evidence from you that you will have the unit installed by an F-Gas qualified engineer. This is a requirement of the Article 11 (5) EC/517/2014 on fluorinated greenhouse gases and The Fluorinated Greenhouse Gases Regulations 2015.