Free Delivery on Orders Over £30
Prices Shown Include 20% UK VAT
Call Us On +44(0)1234 841221

Mitsubishi Heavy Industries FDT Cassette Air Conditioning Inverter Heat Pump A+

Mitsubishi Heavy Industries Air Conditioning FDT100VH + FDC100VSX-W Cassette Hyper 10Kw 3Ph

  • Mitsubishi Heavy Industries Air Conditioning FDT100VH + FDC100VSX-W Cassette Hyper 10Kw 3Ph
  • Mitsubishi Heavy Industries Air Conditioning FDT100VH + FDC100VSX-W Cassette Hyper 10Kw 3Ph
  • Mitsubishi Heavy Industries Air Conditioning FDT100VH + FDC100VSX-W Cassette Hyper 10Kw 3Ph
  • Mitsubishi Heavy Industries Air Conditioning FDT100VH + FDC100VSX-W Cassette Hyper 10Kw 3Ph
  • Mitsubishi Heavy Industries Air Conditioning FDT100VH + FDC100VSX-W Cassette Hyper 10Kw 3Ph

Mitsubishi Heavy Industries Air Conditioning FDT100VH + FDC100VSX-W Cassette Hyper 10Kw 3Ph

£2,981.95 £2,484.96 (ex. VAT)
Stock Status: Sold Out
Sorry, this item is out of stock
Blog

Mitsubishi Heavy Industries Air Conditioning FDC100VSX-W FDT100VH Cassette Heat Pump Hyper Inverter 10Kw/34000Btu A++ R32 380-415V~50Hz 3 Phase

This Kit Includes:

1 of Mitsubishi Heavy Industries Air Conditioning FDT100VH Cassette R32 10Kw

1 of Mitsubishi Heavy Industries Air Conditioning FDC100VSX-W Hyper Inverter Outdoor Unit R32 10Kw R32 3 Phase 415V~50Hz

1 of Mitsubishi Heavy Industries Air Conditioning Eco Touch RC-EX1A Wired Remote Controller 2 wire PAC 

1 of PANEL PART NUMBER T-PSA-5BW-E

Cassette Heat Pumps for Commercial And Residential Applications. Ideal for large open plan areas, or irregular shaped rooms. High efficiency with low noise levels.

Mitsubishi Heavy Industries air conditioning has made a giant leap forward in air conditioning and heat pump technology with the development of the high performance standard cassette range. The Mitsubishi Heavy Industries air conditioning split cassette units are ideal for commercial application such as offices, shops, meeting rooms, restaurants, hotels, clubs, gyms, and open plan areas. The Advanced FDT Cassette range has now been extended to include new small capacity inverter heat pump systems starting at 4Kw, and an extra high capacity system 14Kw at the top end. The 7-Day Programmable Timer now included in standard controls specification.

The improved air flow pattern through the unit and the new design high performance heat exchanger have resulted in a pressure loss reduction, allowing the fan design to be optimised for significantly lower sound levels. The air discharge louver has been modified to minimise air smudging on the ceiling adjacent to the air outlets.



Product Key Feature's:



• 7-Day 24 HR Programmable Timer
• Two on/off settings each day
• Different temperature for each set period
• External timer/BMS switching for Group (up to 16 units)
• Wall Controller - hard wired
• Integral temperature sensor
• Slim 298mm Construction
• Infra-red wireless controller optional
• INVERTER technology
• Low profile attractive grey/white fascia panel
• Improved anti-smudge air discharge
• Low ambient control included
• Auto re-start after power interruption
• Reduced sound levels
• Long pipe-runs up to 50 Meters
• High C.O.P
• Integrated condensate pump


Technical Data:

INDOOR UNIT
PART NUMBER
FDT100VH
PANEL
PART NUMBER
T-PSA-5BW-E
HARD WIRED CONTROLLER
PART NUMBER
RC-EX3A
OUTDOOR UNIT
PART NUMBER
FDC100VSX-W
UK Cooling kW 9.53
UK Sensible Cooling kW 7.65
Cooling Range (Nominal) kW 3.5 to 11.2
S.E.E.R, EER, Energy Label 8, 4.38, A++
Heating Range (Nominal) kW 2.7 to 16.0
S.C.O.P, COP, Energy Label 4.44, 4.45, A+
INDOOR UNIT INDOOR UNIT
Exterior Dimensions (H x W x D) mm 298 x 840 x 840
Net Weight (Including Panel) kg 30
Air Flow (H/M/L) Cooling m3/m 26 / 23 / 17
Air Flow (H/M/L) Heating m3/m 26 / 23 / 17
Sound Pressure Level (H/M/L) Cooling db(A) 39 / 36 / 30
Sound Pressure Level (H/M/L) Heating db(A) 39 / 36 / 29
OUTDOOR UNIT OUTDOOR UNIT
Exterior Dimensions (H x W x D) mm 1300x970x370
Net Weight kg 99
Sound Pressure Level Cooling/Heating db(A) 53/51
ELECTRICAL DATA ELECTRICAL DATA
Power Source Rating MCB A 20A per a phase
Mains Power To Outdoor 3 Phase, 380 - 415V
50Hz
Interconnecting Wires (Dia) (mm2) 3+E (1.5)
Start Current / Max Running Current A 5 / 14
INSTALLATION/REFRIGERANT INSTALLATION/REFRIGERANT
Ref. Piping Size o.d.ins (mm) Liquid 3/8
Suction 5/8
Ref. Min Piping Length m 3*
Ref. Max Piping Length m 100
Vertical Height Difference (Max)
*Outdoor Unit Above/Below Indoor Unit
m 50/15
Refrigerant Amount Pre-charged (kg/TCO2Eq) 4/2.700
* For Pipe Length Up To m 30
Additional Refrigerant g/m 54


PDF Data Sheet:

Page 24 Onwards




MHI Data


These air conditioning units must be installed by an F-Gas qualified engineer.  We can install the unit for you using our F-Gas Certified Engineers. Please note if you do not select our installation service  we will not ship the unit until we have obtained evidence from you that you will have the unit installed by an F-Gas qualified engineer. This is a requirement of the Article 11 (5) EC/517/2014 on fluorinated greenhouse gases and The Fluorinated Greenhouse Gases Regulations 2015.