Mitsubishi Electric Air Conditioning PFD-P500VM-E 2 of PUHY-P250YJM-A Close Control System 415V~50Hz
Mitsubishi Electric’s Close Control System is specifically designed for computer rooms, laboratories etc, where a need for high sensible cooling and close control of temperature and humidity is required. Because of the need for close control 24 hours a day, 365 days a year, an inverter driven compressor has been incorporated into the outdoor unit, maximising the energy efficiency of the PFD series. It can also be connected to a computer network using our AE200 controller, in order to monitor and provide remote email alarms.
Key Product Features:
- High sensible cooling
- Inverter driven capacity control
- EER’s Energy efficient high
- Close control of temperature, ±1ºC
- Easy to install - no service space needed at the rear of the unit
- Quick recovery following power failure
- Return or discharge air temperature control
- Back-up & Rotate function available to PUHY-P250YJM-A
- Connectable stands now available on request
- Optional soft start inverter kit on request
Technical Data:

Indoor PFD-P500VM-E
|
Capacity (kW):
|
|
Heating (Nominal)
|
63.0
|
Cooling (Nominal)
|
56.0
|
Heating (UK)
|
55.4
|
Cooling (UK)
|
51.5
|
SHF R410A (UK)
|
0.93
|
Power Input (kW) Heating (Nominal)
|
5
|
Power Input (kW) Cooling (Nominal)
|
5
|
Airflow(m3/min)
|
320
|
External Static Pressure Pa
|
120
|
Noise (dBA)
|
63
|
Pipe Size Gas mm (in)
|
22.2 (7/8)
|
Pipe Size Liquid mm (in)
|
9.52 (3/8)
|
Width - mm
|
1980
|
Depth - mm
|
780
|
Height - mm
|
1950
|
Weight - kg
|
520
|
Electrical Supply
|
380-415v, 50Hz
|
Phase
|
3
|
Mains Cable No. Cores
|
4 + earth
|
Starting Current (A)
|
68
|
Running Current (A) - Heating
|
8.7
|
Running Current (A) - Cooling
|
8.7
|
Fuse Rating (BS88) - HRC (A)
|
20
|
Piping Restrictions
|
Total Piping Length (m)
|
165
|
Between Indoor and Outdoor Units - Height (m)
|
50
|
2 of Outdoor Unit PUHY-P250YJM-A
|
Capacity (kW):
|
|
Heating (Nominal)
|
31.5
|
Cooling (Nominal)
|
28.0
|
Heating (UK)
|
31.5
|
Cooling (UK)
|
26.6
|
Power Input (kW) Heating (Nominal)
|
7.34
|
Power Input (kW) Cooling (Nominal)
|
7.4
|
Power Input (kW) Heating (UK)
|
9.25
|
Power Input (kW) Cooling (UK)
|
4.26
|
Max No. of Connectable Indoor Units
|
21
|
Airflow(m3/min)
|
170
|
Noise (dBA)
|
58
|
Width - mm
|
920
|
Depth - mm
|
760
|
Height - mm
|
1710
|
Weight - kg
|
200
|
Electrical Supply
|
380-415v, 50Hz
|
Phase
|
3
|
Mains Cable No. Cores
|
4 + earth
|
Starting Current (A)
|
8
|
Running Current (A) - Heating
|
11.3
|
Running Current (A) - Cooling
|
11.4
|
Fuse Rating (BS88) - HRC (A)
|
20
|
Piping Restrictions
|
Total Piping Length (m)
|
1000
|
Furthest Piping Length (m)
|
165
|
Furthest Piping Length after 1st Branch (m)
|
40
|
Between Indoor and Outdoor Units - Height (m)
|
50
|
Between Indoor and Indoor Units - Height (m)
|
15
|
PDF Data:

These air conditioning units must be installed by an F-Gas qualified engineer. We can install the unit for you using our F-Gas Certified Engineers. Please note if you do not select our installation service we will not ship the unit until we have obtained evidence from you that you will have the unit installed by an F-Gas qualified engineer. This is a requirement of the Article 11 (5) EC/517/2014 on fluorinated greenhouse gases and The Fluorinated Greenhouse Gases Regulations 2015.