Mitsubishi Electric Air Conditioning i-NEXT DX 018 M1 S E2 Close Control System 17Kw 415V~50Hz
High precision air conditioners are ideal for applications where high sensible cooling and close control of temperature and humidity are required. The i-NEXT direct expansion air cooled range incorporates full inverter driven BLDC Mitsubishi Electric compressors, perfect for keeping room conditions constant under varying loads, whilst being highly efficient.
Key Product Features:
Perimeter unit with downflow and upflow configurations
Full inverter technology with BLDC Mitsubishi Electric compressors
Ultralight composite EC plug fans resulting in reduced noise and power usage
Integrated control of up to 10 units for intelligent redundancy management
Front access to main components for easy inspection and routine maintenance
Automatic restart from power outage
Return air temperature operating limits up to 40°C
Matched air cooled remote condensers
Optional Modbus RS485 and BACnet TCP/IP connectivity
Optional electrical heater and steam humidifiers
Optional floor stands and discharge plenums
IT Cooling i-NEXT DX
Product Information
IT COOLING
Technical Data:
CRAC UNITS
(Computer Room Air Conditioning)
|
i-NEXT DX 018 M1 S E2
|
|
|
CAPACITY (kW)*2 Range Nominal
|
7.0 - 21.9
17.8
|
SHF Nominal
|
0.99
|
EER*3 Nominal
|
3.7
|
POWER INPUT kw Nominal
|
4.81
|
AIRFLOW (M³/h)
|
4100
|
EXTERNAL STATIC PRESSURE (Pa) Nominal
|
20
|
MAX EXTERNAL STATIC PRESSURE (Pa)
|
315
|
SOUND PRESSURE LEVEL (dB(A))*4
|
From Fan Discharge Downflow / Upflow
|
71.4 / 71.3
|
From Unit Front Downflow / Upflow
|
47.6 / 46.8
|
AIR FILTERS
|
G4
|
DIMENSIONS (mm) Width x Depth x Height
|
785 x 675 x 1925
|
NET WEIGHT (kg) Downflow / Upflow
|
250 / 240
|
POWER SUPPLY (V/Ph/Hz)
|
400/3/50+N
|
MAX RUNNING CURRENT (A)
|
19.7
|
STARTING CURRENT (A)
|
5.3
|
COMPRESSORS
|
BLDC Scroll Inverter
|
PIPE SIZE DIAMETER (mm (in))*6
|
Liquid
|
16 (5/8")
|
Gas
|
18 (3/4")
|
REFRIGERANT
|
R410A
|
REMOTE CONDENSER Standard
|
T-MATE DX-A STD M 25
|
OUTDOOR UNITS
|
T-MATE DX-A STD M 25
|
|
|
DIMENSIONS (mm) Width x Depth x Height
|
1400 x 665 x 1027
|
NET WEIGHT (kg)
|
102
|
AIRFLOW (M³/h)
|
9600
|
POWER SUPPLY (V/Ph/Hz)
|
230 / 1 / 50
|
POWER INPUT (kW) Nominal
|
0.53
|
MAX RUNNING CURRENT (A)
|
2.85
|
SOUND PRESSURE LEVEL (dB(A))
|
1m (ISO3744)
|
67
|
5m
|
56.1
|
10m
|
50.5
|
*1 Down flow version only. *2 Capacity characteristics at 26°C air entering temperature, 40%RH; *condensing temperature 45°C. *3 Remote air cooled condenser not included. *4 1m from unit in free field conditions.
*5 In 2(1+i) configuration, 2 inverter driven with 2 direct online. *6 Recommended nominal pipework sizes for 30m equivalent length. *7 Unit consists of 2 refrigerant circuits. Pipe size shown is per circuit.
PDF Data: