Free Delivery on Orders Over £30
Prices Shown Include 20% UK VAT
Call Us On +44(0)1234 841221

LG Air Conditioning Ducted Heat Pump Standard Inverter

LG Air Conditioning CL12RN20 Concealed Ducted Heat Pump Inverter 3.5Kw/12000Btu A++ R32 240V~50Hz

LG Air Conditioning CL12RN20 Concealed Ducted Heat Pump Inverter 3.5Kw/12000Btu A++ R32 240V~50Hz

£1,369.76 £1,141.47 (ex. VAT)
Stock Status: In Stock
Blog

A++ Rated Energy Product, R32 Refrigerant     



Perfect for areas where you want concealed air conditioning, the Lg air conditioning units are for applications mounted above a ceiling. The Lg ducted air conditioning system is designed for homes, offices, restaurants or shops, the unit operates at low noise levels and is virtually invisible when installed within a suspended ceiling.  Its low unit height (190mm) and lightweight design also helps to make installation easier and more convenient. It's whisper quiet operation is ideal for master bedrooms, living rooms and other single room residential or commercial uses. Available in three sizes, it can be installed in a bulkhead for a different and attractive architectural finish or can be ducted within the space for total integration with the room.
 
The indoor temperature can be checked using the thermistors in the remote controller as well as from the indoor unit. There may be a significant difference between ceiling and floor air temperature. Two thermistors can optimise indoor air temperature for a more comfortable environment. 

LG’s Outdoor Heat Exchanger is coated with a golden anti-corrosive epoxy treatment on the aluminum coil to minimised corrosion. This maintains heat transfer properties of the coil for an extended time where as non-Gold Fin coils progressively lose efficiency due to surface corrosion. Standard on every LG air conditioner, this assists in areas suffering from pollution or near the ocean where the unit may subjected to higher levels of salt.



Auto Changeover:
The air conditioner will switch automatically from cooling to heating modes depending on the set temperature.




Product Key Feature's:


• Anti Corrosion Gold Fin (Outdoor)
• Weekly Program
• Low Standby Power
• Central Controller (Accessory)
• Child Lock Function
• Two Thermistor Control
• Optimal Air Distribution
• Auto Restart
• Auto Operation
• Quiet Operation
• Healthy Dehumidification
• Hot Start
• 24-Hour ON/OFF Setting Timer
• R32 Refrigerant  




Technical Information:


 

INDOOR

CL12R N20

Capacity

Cooling                Min / Nom / Max

kW

1.4 / 3.4 / 3.9

Heating

Min / Nom / Max

kW

1.6 / 4.0 / 4.7

Low Temperature Capacity

Heating -7°C            Max

kW

4.4

Power Input (Set)

Cooling                    Nom

kW

0.99

Heating

Nom

kW

1.00

Power Input (Indoor)

Min / Max (ESP 2.5mmAq)

W

80 / 95

Min / Max (ESP 5.0mmAq)

W

80 / 100

Running Current

Cooling / Heating    Nom

A

4.2 / 4.6

Power Supply

Ø / V / Hz

1 / 220-240 / 50

EER

3.42

COP

4.00

SEER

6.28

SCOP

4.00

Pdesign (@-10°C)

kW

3.0

Seasonal Energy Label

Cooling / Heating (A++ to E Scale)

A++ / A+

Annual Energy Consumption

Cooling / Heating

kWh

189 / 1,050

Piping Connection

Liquid

mm (inch)

Ø 6.35 (1/4)

Gas

mm (inch)

Ø 9.52 (3/8)

Drain

O.D. / I.D.

mm

32.0 / 25.0

Air Flow Rate

High / Medium / Low

m3/min

10.0 / 8.5 / 7.0

Sound Pressure

Cooling

High / Medium / Low

dBA

31 / 28 / 27

Sound Power

Cooling

Max

dBA

55

Dehumidification Rate

l/h

1.1

Dimensions

Body

W x H x D

mm

900 x 190 x 700

Net Weight

Body

kg

24.0

External Static Pressure

Min ~ Max

mmAq (Pa)

0~5 (0~49)


OUTDOOR

UU12WR UL0

Compressor                                     Type

Twin Rotary

Airflow Rate

Nom

m3/min

32

Sound Pressure

Cooling

Nom

dBA

49

Heating

Nom

dBA

52

Sound Power                         Cooling

Max

dBA

65

Dimensions                            W x H x D

mm

770 x 545 x 288

Net Weight

kg

33.8

Refrigerant

Type

R32

Charge

g

900

Additional Charge (after 7.5m)

g/m

20

GWP

675

t-CO2  eq

0.61

Operation Range (Outdoor)

Cooling

Min ~ Max

°C DB

-15 ~ 48

Heating

Min ~ Max

°C WB

-18 ~ 18

Power Supply

Ø / V / Hz

1 / 220-240 / 50

Power Supply Cable

No. x mm2

3C x 2.5

Transmission Cable

No. x mm2

4C x 0.75

Circuit Breaker

A

15

Piping Length Total

Min ~ Max

m

5~20

Piping Elevation Difference  IDU - ODU

Max

m

10

Piping Connection

Liquid

mm (inch)

Ø 6.35 (1/4)

Gas

mm (inch)

Ø 9.52 (3/8)






PDF Data:
 


    



These air conditioning units must be installed by an F-Gas qualified engineer.  We can install the unit for you using our F-Gas Certified Engineers. Please note if you do not select our installation service  we will not ship the unit until we have obtained evidence from you that you will have the unit installed by an F-Gas qualified engineer. This is a requirement of the Article 11 (5) EC/517/2014 on fluorinated greenhouse gases and The Fluorinated Greenhouse Gases Regulations 2015.

Not yet reviewed
Write an online review and share your thoughts with other shoppers!
Be the first to review this product