The Advanced Fujitsu air conditioning AUXG CIRCULAR FLOW cassette range has now been extended to include new smaller capacity INVERTER system starting at 5kW / 17000Btu, and an high efficiency system 16kW / 54000Btu at the top end of the range. The new touch screen 7-Day Programmable Timer now included in standard controls specification and multi programmable 24Hr control. Fujitsu air conditioning and heat pump high performance inverter compact cassette series split systems designed for residential and commercial application such as offices, shops, meeting rooms, restaurants, hotels, clubs, gyms, and open plan areas.
The New Cassette type realizes Circular Flow to blow large airflow in 360º direction by mounting high performance DC fan motor, new turbo fan and unique seamless airflow louver design. Each louver can be set individually by Touch Panel Wired Remote Controller to enjoy the comfort of different directional airflow's according to various room layouts. Energy saving operation starts automatically by detecting the motion of a person. 2 modes of save operation mode and stop mode can be selected.
In order to be able to adapt to the shape of the room to be conditioned, the Fujitsu air conditioning cassette units are able to configure the air impulsion in two, three or four different directions and thus achieve uniform air conditioning. The unit can make a sweep using its deflector slats to air-condition the premises more quickly. The direction of the sweep as well as the auto swing function can be selected by using the remote control. Models with a movable rosette incorporate weekly programming control that allows on and off programming up to twice a day.
Auto Changeover: The air conditioner will switch automatically from cooling to heating modes depending on the set temperature. Optimized Cooling & Heating Air Flow: The air vanes will be adjusted according to the mode of operation. In heating mode air will be distributed at a lower angle due to hot air rising. Swirl Swing: Swirl swing distributes air evenly throughout the room to ensure a more comfortable conditioned environment by adjusting the movement of the louvers.
Product Key Feature's
• High Head Drain Pump 850mm
• Auto Changeover (heating and cooling)
• Low Standby Power (switch mode)
• Auto Restart after power outage
• Easy-to-Clean Air Filter
• Two Thermistor Temperature Control (Controller and Unit)
• Optimal Louver Air Distribution control
• Auto Operation
• Quiet Operation
• Healthy De-humidification
• Hot Start on heat mode
• 24-Hour ON/OFF Setting Timer With Weekly Program
• Optimal air distribution with a directional Air flow system.
• Auto Louver Swing
Other Controller Features
- New multi programming of different operating schedules each day.
- On and off programming over the day.
- Set the time in periods of five minutes.
- Cancellation of operation on a specific day (public holiday)
Technical Data
Model No.
|
Indoor unit
|
AUXG45LRLB
|
AUXG54LRLB
|
Outdoor unit
|
AOYG45LBTA
|
AOYG54LBTA
|
Power Source
|
|
Single-phase, ~230V, 50Hz
|
Capacity
|
Cooling
|
kW
|
12.5 (4.0-14.0)
|
13.3 (4.5-14.5)
|
Heating
|
14.0 (4.2-16.2)
|
15.8 (4.7-16.5)
|
Input Power
|
Cooling/Heating
|
kW
|
3.85/3.73
|
4.38/4.58
|
EER
|
Cooling
|
W/W
|
3.25
|
3.04
|
COP
|
Heating
|
3.75
|
3.45
|
Pdesign
|
Cooling/Heating(-10°C)
|
kW
|
-
|
-
|
SEER
|
Cooling
|
W/W
|
-
|
-
|
SCOP
|
Heating (Average)
|
-
|
-
|
(QHUJ\ (IÀFLHQF\
Class
|
Cooling
|
-
|
-
|
Heating (Average)
|
-
|
-
|
Max. Operating Current
|
Cooling/Heating
|
A
|
20.5/20.5
|
21.5/21.5
|
Annual Energy Consumption
|
Cooling
|
kWh/a
|
-
|
-
|
Heating
|
-
|
-
|
Moisture Removal
|
|
I/h
|
4.5
|
5.0
|
Sound Pressure Level
|
Indoor (Cooling)
|
H/M/L/Q
|
dB(A)
|
46/42/39/35
|
47/43/40/36
|
Indoor (Heating)
|
H/M/L/Q
|
46/42/39/35
|
47/43/40/36
|
Outdoor(Cooling/Heating)
|
High
|
55/55
|
55/57
|
Sound Power Level
|
Indoor(Cooling/Heating)
|
High
|
60/60
|
61/61
|
Outdoor(Cooling/Heating)
|
High
|
68/68
|
69/71
|
$LUÁRZ 5DWH
|
Indoor / Outdoor
|
High
|
m3/h
|
2000/6750
|
2100/6750
|
Net Dimensions H x W x D Weight
|
Indoor
|
mm
|
288×840×840
|
288×840×840
|
kg(lbs)
|
29 (64)
|
29 (64)
|
Outdoor
|
mm
|
1290×900×330
|
1290×900×330
|
kg(lbs)
|
86 (189)
|
86 (189)
|
Connection Pipe Diameter (Liquid / Gas)
|
mm
|
9.52/15.88
|
9.52/15.88
|
Drain hose Diameter (I.D./O.D.)
|
25/32
|
25/32
|
Max Pipe Length (Pre-Charge)
|
m
|
50 (20)
|
50 (20)
|
Max Height Difference
|
30
|
30
|
Operation Range
|
Cooling
|
°CDB
|
-15 to 46
|
-15 to 46
|
Heating
|
-15 to 24
|
-15 to 24
|
Refrigerant
|
Type (Global Warming Potential)
|
R410A (2,088)
|
R410A (2,088)
|
Charge
|
g
|
3,350
|
3,350
|
Cassette Grille
(to be ordered separately)
|
Model name
|
UTG-UKYA-W
|
UTG-UKYA-W
|
Dimensions (H × W × D)
|
mm
|
53×950×950
|
53×950×950
|
Weight
|
kg(lbs)
|
6.0 (13)
|
6.0 (13)
|
System List Price
|
£
|
3033
|
3522
|
PDF Data Sheet:
These air conditioning units must be installed by an F-Gas qualified engineer. We can install the unit for you using our F-Gas Certified Engineers. Please note if you do not select our installation service we will not ship the unit until we have obtained evidence from you that you will have the unit installed by an F-Gas qualified engineer. This is a requirement of the Article 11 (5) EC/517/2014 on fluorinated greenhouse gases and The Fluorinated Greenhouse Gases Regulations 2015.