Free Delivery on Orders Over £30
Prices Shown Include 20% UK VAT
Call Us On +44(0)1234 841221

Daikin Air Curtains

Daikin Heat Pump Air Curtain CYQS250DK140*BN/*SN 14kW / 48000Btu 230V~50hZ

Daikin Heat Pump Air Curtain CYQS250DK140*BN/*SN 14kW / 48000Btu 230V~50hZ

£6,195.07 £5,162.56 (ex. VAT)
Stock Status: In Stock
Daikin Heat Pump Air Curtain CYQS250DK140*BN/*SN 14kW / 48000Btu 230V~50hZ

Air Curtains for light commercial applications.

Daikin standard air curtains are the ideal solution for retailers and consultants to combat the issue of climate seperatiom across their outlet or office doorway. Using a combination of rectifier technology, optimised air velocity and temperature control, they deliver greater comfort to staff and customers alike, all year roumd, in all weathers. In conjunction with Biddle, Daikin now offer the best air curtain to the market, coupling the benefits of the Biddle air curtain technology with the benefits of the Daikin heat pump inverter technology. 

Technical Specifications

 
Technical Specifications CYQS250DK140*BN/*SN
Heating capacity Installation level B speed 2 kW 12.7
speed 3 kW 16.2
Delta T inlet = room temperature speed 2 K 18
speed 3 K 16
Power Input (50Hz) Fan only kW 0.58
Heating kW 0.58
Maximum door width m 2.5
Maximum door height Favorable conditions m 2.3
Normal conditions m 2.15
Unfavorable  conditions m 2
Dimensions Height Unit F mm 270
Unit C mm 270
Unit R mm 270
Width Unit F mm 2,500
Unit C mm 2,500
Unit R mm 2,548
Depth Unit F mm 590
Unit C mm 821
Unit R mm 561
Packed unit Height mm 760
Width mm 2,630
Depth mm 680
Weight Unit F kg 107
Unit C kg 129
Unit R kg 137
Packed unit F kg 145
Packed unit C kg 182
Packed unit R kg 190
Casing Colour BN:RAL9010
Material Electrogalvanised sheet steel
Required Ceiling Void mm 420
Fan - Air flow rate - Heating Installation level B speed 2 m³/h 2,058
speed 3 m³/h 2,910
Refrigerant Type R-410A
Control Electronic expansion valve
Sound pressure level - Heating Installation level B speed 2 dBA 41
speed 3 dBA 51
Piping connections Liquid (OD) Diameter (OD) mm 9.52
Gas Diameter (OD) mm 19
Air Filter Vacuum cleanable filter G1
Required  accessories Daikin wired remote control (BRC1E51A or BRC1D52)
Notes Favorable conditions: covered shopping mall or revolving-door entrance. Normal conditions: little direct wind, no opposite open doors, building with ground floor only. Unfavorable conditions: location at a corner or square, multiple floors and/or open stairway.
Pipe work and electrical connections are on top of the unit
Sound pressure level (at 3m)
Installation level B: standard setting, refer to the databook or installation manual for more information (only one installation level available)
*F = Free Hnging, C = Cassette, R = Recessed.

Electrical Specifications

 
Electrical Specifications CYQS250DK140*BN/*SN
Power Supply Frequency Hz 50
Voltage V 230
Voltage range Min. V 224
Max. V 240
Current (50Hz) Maximum fuse amps (MFA) A 16
Full load amps (FLA) A 2.10