Free Delivery on Orders Over £30
Prices Shown Include 20% UK VAT
Call Us On +44(0)1234 841221

Daikin Air Conditioning VRV IV Heat Pump Inverter

Daikin Air Conditioning RQCEQ280P3 VRV IV-Q (RQEQ140P+ RQEQ140P) Heat Pump Recovery 3-pipe Condensing Unit 415V~50Hz

Daikin Air Conditioning RQCEQ280P3 VRV IV-Q (RQEQ140P+ RQEQ140P) Heat Pump Recovery 3-pipe Condensing Unit 415V~50Hz

£9,395.76 £7,829.80 (ex. VAT)
Stock Status: In Stock
Blog

Outdoor unit module set: RQEQ140P+ RQEQ140P


Due to significant developments in heat pump technology, today’s air conditioning systems, running on R-410A refrigerant, offer better performances than R-22 and R-407C systems did in the past. Furthermore, R-22 will be soon unavailable in Europe. Already today, only reclaimed or recycled R-22 can be used for servicing. To upgrade R-22 and R-407C systems as cost effectively as possible, Daikin units can be installed using existing pipe work. Replacement technology is available for residential and commercial applications.

It is not necessary to remove the existing piping and even the indoor units can remain (depending on type of indoor unit). This means work only has to be carried out at the outdoor unit and not inside your building in case of a heat pump installation. The outdoor unit automatically charges the refrigerant and cleans the refrigerant piping. This unique Daikin feature makes the installation time even shorter.



Technical Data:



 
OUTDOOR SYSTEM RQCEQ280P
System Outdoor unit module 1 RQEQ140P
Outdoor unit module 2 RQEQ140P
Outdoor unit module 3
Outdoor unit module 4 -
Capacity range HP 10
Cooling capacity Nom. kW 28.0
Heating capacity Nom. kW 32.0
Power input - 50Hz Cooling Nom. kW 7.04
Heating Nom. kW 8.00
EER 3.98
COP 4.00
Maximum number of connectable indoor units 21
Sound pressure level Cooling Nom. dBA 57
Piping connections Liquid OD mm 9.52
Gas OD mm 22.2
Discharge gas OD mm 19.1
Piping length OU - IU Max. m 120
Total piping length System Actual m 300
Level difference OU - IU m 50 (outdoor unit in highest position)
Current - 50Hz Maximum fuse amps (MFA) A 30
 
OUTDOOR UNIT MODULE RQEQ140P
Dimensions Unit HeightxWidthxDepth mm 1,680x635x765
Weight
Sound pressure level
Unit kg 175
Cooling Nom. dBA 54
Operation range Cooling Min.~Max. °CDB -5~43
Heating Min.~Max. °CWB -20~15
Refrigerant Type R-410A
Power supply Phase/Frequency/Voltage Hz/V 3~/50/380-415

These air conditioning units must be installed by an F-Gas qualified engineer.  We can install the unit for you using our F-Gas Certified Engineers. Please note if you do not select our installation service  we will not ship the unit until we have obtained evidence from you that you will have the unit installed by an F-Gas qualified engineer. This is a requirement of the Article 11 (5) EC/517/2014 on fluorinated greenhouse gases and The Fluorinated Greenhouse Gases Regulations 2015.

Not yet reviewed
Write an online review and share your thoughts with other shoppers!