A+ Energy rated product
Includes:
1 x Daikin RZASG125M7V1 Outdoor unit R32
1 x Daikin FUA125A Under Ceiling Cassette R32
1 x Daikin Remote Controller Hard Wired
Daikin’s Under Ceiling Cassette is a unique product, a 4 way blow system that can be installed under the ceiling in rooms that have solid ceilings or narrow voids that may prevent a traditional cassette being installed. Under Ceiling Cassette Seasonal Smart. The Under Ceiling Cassette exceeds Energy Related Products Directive minimum efficiency standards for Seasonal Efficiency, combining industry leading efficiencies with smart looks and functionality to suit office and retail applications.
The re-designed profile of the unit means it is less obtrusive when installed. Air discharge Louvre's close completely when the unit is not operating, adding to the aesthetic. Energy savings can be made using the remote controller which gives control over set-point ranges and day-to-day use of controls. This can give occupants some flexibility over room conditions without compromising energy usage. Energy efficiencies can be improved by utilising the selectable evaporating and condensing temperature option, making the Seasonal Smart Under Ceiling Cassette the ideal solution for energy conscious building managers.
Product Key Feature's:
• High CoP, up to record 3.76
• High Air movement volume
• Fixed wall mounted controller
• Slim construction
• Pipe runs up to 75 meters
• Low noise levels
• Back-up switch for loss of controller
• Cold draft prevention on heat pump start up
• Fault diagnosis
• Auto re-start after power interruption
• PRE-CHARGED WITH REFRIGERANT for up to 30 metres pipe length
Product Technical Data:
Indoor Units
|
|
FUA125A
|
Capacity
|
UK Total Cooling kW
|
13.60
|
UK Sensible Cooling kW
|
9.30
|
Nominal Cooling kW
|
12.00
|
Nominal Heating kW
|
13.50
|
Seasonal Efficiency (EN14825) COOLING
|
Energy Label
|
A+
|
Pdesign kW
|
12.00
|
SEER
|
5.61
|
Annual Energy Consumption kWh
|
749
|
Seasonal Efficiency (EN14825) HEATING
|
Energy Label
|
A+
|
Pdesign kW
|
14.13
|
SCOP
|
4.44
|
Annual Energy Consumption kWh
|
4456
|
Nominal Efficiency
|
EER / COP
|
3.39 / 3.42
|
Energy Label
|
A / A
|
Annual Energy Consumption kWh
|
1770
|
Air Flow Rate (Cooling) High / Nom / Low m3/sec
|
0.542 / 0.442 /
0.342
|
Dimensions
|
Height mm
|
198
|
Width mm
|
950
|
Depth mm
|
950
|
Weight kg
|
26
|
Sound Pressure (Cooling) High / Nom / Low dBA
|
47 / 43 / 40
|
Sound Power dBA
|
65
|
Model
|
RZASG125M7V1
|
Casing
|
Colour
|
|
Ivory white
|
|
Material
|
|
Painted galvanized steel plate
|
Dimensions
|
Unit
|
Height
|
mm
|
990
|
|
|
Width
|
mm
|
940
|
|
|
Depth
|
mm
|
320
|
|
Packed unit
|
Height
|
mm
|
1,170
|
|
|
Width
|
mm
|
1,015
|
|
|
Depth
|
mm
|
422
|
Weight
|
Unit
|
kg
|
70
|
|
Packed unit
|
kg
|
79
|
Packing
|
Weight
|
kg
|
9
|
Heat exchanger
|
Fin
|
Type
|
|
WF fin
|
|
|
Treatment
|
|
Anti-corrosion treatment (PE)
|
Fan
|
Type
|
|
Propeller
|
|
Discharge direction
|
|
Horizontal
|
|
Quantity
|
|
1
|
|
Air flow rate
|
Cooling
|
Nom.
|
m³/min
|
71
|
|
|
Heating
|
Nom.
|
m³/min
|
82
|
|
|
|
Partial
|
m³/min
|
55 (1)
|
Fan motor
|
Quantity
|
|
1
|
|
Model
|
|
Brushless DC motor
|
|
Output
|
W
|
200
|
|
Drive
|
|
Direct drive
|
Compressor
|
Quantity
|
|
1
|
|
Type
|
|
Hermetically sealed swing compressor
|
Operation range
|
Cooling
|
Ambient
|
Min.
|
°CDB
|
-15
|
|
|
|
Max.
|
°CDB
|
46
|
|
Heating
|
Ambient
|
Min.
|
°CWB
|
-15
|
|
|
|
Max.
|
°CWB
|
15.5
|
Sound power level
|
Cooling
|
dBA
|
71
|
|
Heating
|
dBA
|
71 (1)
|
Sound pressure level
|
Cooling
|
Nom.
|
dBA
|
53
|
|
Heating
|
Nom.
|
dBA
|
57
|
Refrigerant
|
Type
|
|
R-32
|
|
Charge
|
kg
|
2.60
|
|
Charge
|
TCO2Eq
|
1.76
|
|
Control
|
|
Expansion valve (electronic type)
|
|
GWP
|
|
675
|
|
Circuits
|
Quantity
|
|
1
|
Refrigerant oil
|
Type
|
|
FW68DA
|
|
Charged volume
|
l
|
0.90
|
Piping connections
|
Liquid
|
Quantity
|
|
1
|
|
|
Type
|
|
Flare connection
|
|
|
OD
|
mm
|
9.52
|
|
Gas
|
Quantity
|
|
1
|
|
|
Type
|
|
Flare connection
|
|
|
OD
|
mm
|
15.9
|
|
Drain
|
Quantity
|
|
5
|
|
|
Type
|
|
Hole
|
|
|
OD
|
mm
|
26
|
|
Piping length
|
OU - IU
|
Min.
|
m
|
5
|
|
|
|
Max.
|
m
|
50
|
|
|
System
|
Equivalent
|
m
|
70
|
|
|
|
Chargeless
|
m
|
30
|
|
Additional refrigerant charge
|
kg/m
|
See installation manual
|
|
Level difference
|
IU - OU
|
Max.
|
m
|
30.0
|
|
|
IU - IU
|
Max.
|
m
|
0.5
|
|
Heat insulation
|
|
Both liquid and gas pipes
|
Defrost method
|
Reversed cycle
|
Defrost control
|
Sensor for outdoor heat exchanger temperature
|
Capacity control
|
Method
|
|
Inverter controlled
|
PED
|
Category
|
|
Category II
|
Safety devices
|
Item
|
01
|
|
High pressure switch
|
|
|
02
|
|
Low pressure switch
|
|
|
03
|
|
Fan driver overload protector
|
|
|
04
|
|
Fuse
|
|
|
05
|
|
Compressor motor thermal protector
|
Standard Accessories
|
Tie-wraps
|
2
|
|
Installation manual
|
1
|
|
Refrigerant label for F-gas regulation
|
1
|
|
General safety precautions
|
1
|
|
LOT10 Energy Label
|
1
|
|
Peel off F-gas label
|
|
Power supply
|
Name
|
|
V1
|
|
Phase
|
|
1~
|
|
Frequency
|
Hz
|
50
|
|
Voltage
|
V
|
220-240
|
|
Voltage range
|
Min.
|
V
|
198
|
|
|
Max.
|
V
|
264
|
Current
|
Zmax
|
List
|
|
Complies to EN61000-3-11
|
|
Minimum Ssc value
|
kVa
|
Equipment complying with EN / IEC 61000-3-12, See note 2, See note 3
|
Wiring connections
|
For power supply
|
Remark
|
|
See installation manual outdoor unit
|
|
For connection with indoor
|
Remark
|
|
See installation manual outdoor unit
|
Power supply intake
|
See installation manual outdoor unit
|
Current - 50Hz
|
Maximum fuse amps (MFA)
|
A
|
32
|
Notes
|
(1) - According to ENER Lot 21
|
|
(2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase.
|
|
(3) - Ssc: Short-circuit power
|
|
(4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase.
|
PDF Data:
These air conditioning units must be installed by an F-Gas qualified engineer. We can install the unit for you using our F-Gas Certified Engineers. Please note if you do not select our installation service we will not ship the unit until we have obtained evidence from you that you will have the unit installed by an F-Gas qualified engineer. This is a requirement of the Article 11 (5) EC/517/2014 on fluorinated greenhouse gases and The Fluorinated Greenhouse Gases Regulations 2015.