FCAG35B / RXM35N9
|
Indoor unit
|
FCAG35BVEB
|
Outdoor unit
|
RXM35N2V1B9
|
Cooling capacity
|
Nom.
|
kW
|
3.50
|
|
Nom.
|
Btu/h
|
11,900
|
|
Nom.
|
kcal/h
|
3,009
|
Heating capacity
|
Nom.
|
kW
|
4.20
|
|
Nom.
|
Btu/h
|
14,300
|
|
Nom.
|
kcal/h
|
3,611
|
Power input
|
Cooling
|
Nom.
|
kW
|
0.94
|
|
Heating
|
Nom.
|
kW
|
1.11
|
Nominal efficiency
|
EER
|
|
3.72
|
|
COP
|
|
3.77
|
|
Annual energy consumption
|
kWh
|
470
|
|
Energy labeling Directive
|
Cooling
|
|
A
|
|
|
Heating
|
|
A
|
Space cooling
|
Energy efficiency class
|
|
A++
|
|
Capacity
|
Pdesign
|
kW
|
3.50
|
|
SEER
|
|
6.35
|
|
Annual energy consumption
|
kWh/a
|
193
|
|
A Condition (35°C - 27/19)
|
Pdc
|
kW
|
3.50
|
|
|
EERd
|
|
3.72
|
|
|
Power input
|
kW
|
0.94
|
|
B Condition (30°C - 27/19)
|
Pdc
|
kW
|
2.60
|
|
|
EERd
|
|
5.33
|
|
|
Power input
|
kW
|
0.49
|
|
C Condition (25°C - 27/19)
|
Pdc
|
kW
|
1.68
|
|
|
EERd
|
|
9.52
|
|
|
Power input
|
kW
|
0.18
|
|
D Condition (20°C - 27/19)
|
Pdc
|
kW
|
1.49
|
|
|
EERd
|
|
12.25
|
|
|
Power input
|
kW
|
0.12
|
Space heating (Average climate)
|
Energy efficiency class
|
|
A++
|
|
Capacity
|
Pdesign
|
kW
|
3.32
|
|
SCOP/A
|
|
4.90
|
|
SCOPnet/A
|
|
4.96
|
|
Pdh Heating capacity at -10°
|
kW
|
2.60
|
|
Annual energy consumption
|
kWh/a
|
948
|
|
Required back up heating cap at design conditions
|
kW
|
0.72
|
|
TOL
|
Tol (temperature operating limit)
|
°C
|
-15
|
|
|
Pdh (declared heating cap)
|
kW
|
2.04
|
|
|
COPd (declared COP)
|
|
2.50
|
|
|
Power input
|
kW
|
0.82
|
|
TBivalent
|
Tbiv (bivalent temperature)
|
°C
|
-7
|
|
|
Pdh (declared heating cap)
|
kW
|
2.94
|
|
|
COPd (declared COP)
|
|
3.10
|
|
|
Power input
|
kW
|
0.95
|
|
A Condition (-7°C)
|
Pdh (declared heating cap)
|
kW
|
2.94
|
|
|
COPd (declared COP)
|
|
3.10
|
|
|
Power input
|
kW
|
0.95
|
|
B Condition (2°C)
|
Pdh (declared heating cap)
|
kW
|
1.79
|
|
|
COPd (declared COP)
|
|
4.98
|
|
|
Power input
|
kW
|
0.36
|
|
C Condition (7°C)
|
Pdh (declared heating cap)
|
kW
|
1.15
|
|
|
COPd (declared COP)
|
|
6.20
|
|
|
Power input
|
kW
|
0.19
|
|
D Condition (12°C)
|
Pdh (declared heating cap)
|
kW
|
1.24
|
|
|
COPd (declared COP)
|
|
7.88
|
|
|
Power input
|
kW
|
0.16
|
Space heating (Warm climate)
|
Energy efficiency class
|
|
A+++
|
|
Capacity
|
Pdesignh
|
kW
|
1.79
|
|
SCOP
|
|
6.27
|
|
SCOPnet
|
|
6.36
|
|
Annual energy consumption
|
kWh/a
|
400
|
|
Required back up heating cap at design conditions
|
kW
|
0.00
|
|
TOL
|
Tol (temperature operating limit)
|
°C
|
-15
|
|
|
Pdh (declared heating cap)
|
kW
|
2.04
|
|
|
COPd (declared COP)
|
|
2.50
|
|
|
Power input
|
kW
|
0.82
|
|
TBivalent
|
Tbiv (bivalent temperature)
|
°C
|
2
|
|
|
Pdh (declared heating cap)
|
kW
|
1.79
|
|
|
COPd (declared COP)
|
|
4.98
|
|
|
Power input
|
kW
|
0.36
|
|
B Condition (2°C)
|
Pdh (declared heating cap)
|
kW
|
1.79
|
|
|
COPd (declared COP)
|
|
4.98
|
|
|
Power input
|
kW
|
0.36
|
|
C Condition (7°C)
|
Pdh (declared heating cap)
|
kW
|
1.15
|
|
|
COPd (declared COP)
|
|
6.20
|
|
|
Power input
|
kW
|
0.19
|
|
D Condition (12°C)
|
Pdh (declared heating cap)
|
kW
|
1.24
|
|
|
COPd (declared COP)
|
|
7.88
|
|
|
Power input
|
kW
|
0.16
|
Power consumption in other than active mode
|
Crankcase heater mode
|
Cooling
|
PCK
|
kW
|
0.000
|
|
|
Heating
|
PCK
|
kW
|
0.000
|
|
Off mode
|
Cooling
|
POFF
|
kW
|
0.014
|
|
|
Heating
|
POFF
|
kW
|
0.014
|
|
Standby mode
|
Cooling
|
PSB
|
kW
|
0.014
|
|
|
Heating
|
PSB
|
kW
|
0.014
|
|
Thermostat-off mode
|
Cooling
|
PTO
|
kW
|
0.007
|
|
|
Heating
|
PTO
|
kW
|
0.007
|
Cooling
|
Cdc (Degradation cooling)
|
|
0.25
|
Heating
|
Cdh (Degradation heating)
|
|
0.25
|
Cooling function included
|
Yes
|
Heating function included
|
Yes
|
Average climate included
|
Yes
|
Cold season included
|
No
|
Warm season included
|
Yes
|
Eurovent
|
Sound power level outdoor
|
Cooling
|
Nom.
|
dBA
|
61
|
|
Sound power level indoor
|
Cooling
|
Nom.
|
dBA
|
49
|
|
Piping length
|
Cooling
|
Measuring condition
|
m
|
5.00
|
Notes
|
(1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
|
|
(2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
|
|
(3) - See separate drawing for operation range
|
|
(4) - See separate drawing for electrical data
|