Free Delivery on Orders Over £30
Prices Shown Include 20% UK VAT
Call Us On +44(0)1234 841221

Floor Standing Cabinet Heater

Combat ELG235 Natural Gas And LPG Fixed Elite Cabinet Heater 236Kw/800000Btu 415V~50Hz

Combat ELG235 Natural Gas And LPG Fixed Elite Cabinet Heater 236Kw/800000Btu 415V~50Hz

£8,996.00 £7,496.67 (ex. VAT)
Stock Status: In Stock
Blog
Combat ELG235 Natural Gas And LPG Fixed Elite Cabinet Heater 236Kw/800000Btu 415V~50Hz

FOR HEATING LARGE PREMISES WITH MINIMUM INSTALLATION REQUIREMENTS

Running on natural gas or LPG, the fixed Combat ELG space heater range are the most functional and efficient alternative to traditional heating plants, also as a solution for intermittent or occasional use. Heating power, flexible use and low running costs make them ideal for heating large spaces such as industrial areas, large sheds, workshops, warehouses, laboratories, showrooms, supermarkets, religious buildings, gyms and tension structures. Where there is a need for the heater to be connected to fresh air or air from an adjacent area for its intake of distribution air, inlet duct connections can be provided. For all oil fired heaters, an oil line connection kit comprising of a gate valve, spring operated fire valve, oil filter and connecting nipples are supplied for installation on site.

 

Key Product Features:


• Combat Elite Cabinet Heaters are fitted witha packaged burner, utilising two stage technology.
• Gas options Natural Gas (G20) (standard) and LPG G31 (upon request).
• Each heater is supplied with the Combat NRG Control, fitted to the heater and pre-wired.
• Electric board
• Reduced Flue Size 130mm with self-sealing spigot push in
• Centrifugal fan
• Air inlet grills
• Where there is a need for the heater to be connected to fresh air or air from an adjacent area for its intake of distribution air, inlet duct
connections can be provided.
• Body thermo-acoustic insulation and safe low surface temperature
• Stainless steel combustion chamber with aerodynamic shape
• High efficiency heat exchanger
• New sleek distribution head shape
• On request bio-gas feeding




Technical Data:
 

Model

Unit

75

105

135

185

235

'A' Width

mm

723

857

857

1,016

1,016

'B' Depth cabinet only

mm

860

860

1015

1676

1676

'C' Height cabinet only

mm

1,734

1,925

1,925

1,925

1,925

'D' Depth overall

mm

1,370

1,380

1,490

2,255

2,255

'E' Height incl.heads

mm

2,038

2,230

2,230

2,230

2,230

'F' Left/Right hand air inlet spigot - height

mm

781

781

940

1600

1600

'G' Left/Right hand air inlet spigot - Depth

mm

457

457

560

560

560

'H' Rear air inlet spigot - Depth

mm

648

781

781

N/A

N/A

'J' Rear air inlet spigot - height

mm

361

446

446

N/A

N/A

Weight

kg

200

245

270

440

440

Flue Diameter

mm

130

130

130

130

130

Flue Length

m

8

8

8

8

8

Heater Clearances to Combustibles (mm)
 

To Side of Heater

To Rear of Heater

To Front of Heater

For Air Distribution

600

600

2,000

4,000

Model

Stage

Unit

75

105

135

185

235

Maximum Heater Input- Gross

High Fire

[kW]

93.0

128.0

162.0

225.0

285.0

Low Fire

47.0

65.0

81.0

112.0

141.0

Net Heat Input

High Fire

[kW]

83.8

115.3

146.0

202.7

256.8

Low Fire

42.3

58.6

73.0

100.9

127.0

Maximum Heat Output

High Fire

[kW]

76.7

104.3

133.4

186.5

236.8

Low Fire

40.5

56.3

70.0

95.9

112.5

Maximum Gas Rate Natural (G20)

High Fire

[m3/h]

8.4

11.6

14.3

20.3

25.7

Low Fire

4.3

5.8

7.2

10.1

12.6

Maximum Gas Rate LPG Propane (G31)

High Fire

[m3/h]

3.5

4.8

5.9

8.5

10.6

Low Fire

1.8

2.4

3.0

4.2

5.2

Inlet Pressure Natural Gas (G20)

[mbar]

20

20

20

20

20

Minimum 17 mbar

Maximum 25 mbar

Inlet Pressure LPG Propane Gas (G31)

[mbar]

37

37

37

37

37

Minimum 25 mbar

Maximum 45 mbar

Gas Connection

Inches BSP

3/4

1 1/4

General Data

Model

Unit

75

105

135

185

235

Electrical  Supply*

230v 50Hz

1 Phase

400v 50Hz 3 Phase

Main Fan Motor Type

Direct Drive

Belt Drive

Motor Size

kW

0.75

2.2

1.5

2.2

Start Current

[A]

11.5

9.0

10

10.0

24.0

Run Current

[A]

6.5

5.0

3.7

3.7

5.1

Airflow - Free Blowing

[m3/h]

5,200

8,600

8,600

11,200

14,200



PDF Data Sheet:






​​​​​​​

Not yet reviewed
Write an online review and share your thoughts with other shoppers!
Be the first to review this product