Power Inverter Heat Pump
| Mitsubishi Electric Mr Slim PKA-RP60GAL (6Kw) designed for applications with long piperuns. The PKA-RP60GAL inverter can do 50 Meters piperun while delivering 6 Kw of power. These systems can reuse existing pipework even if the pipe was using old R22 or R407c Refrigerants. |
| Advanced inverter technology makes the Mr Slim Power Inverter the number one choice for improving comfort. They provide energy savings of up to 70% annually when compared to a previous non-inverter model. Operating noise has also been reduced thanks to improvements in fan design, while existing pipe work is reusable for easier maintenance and installation. |
Product Key Feature's
• High CoP, up to 3.87
• Advanced technology control
• Infra-red controller with wall mounting bracket
• Slim construction
• Pipe runs up to 50 metres
• Low noise – 49dBA
• Back-up switch for loss of controller
• Cold draft prevention on heat pump start up
• Fault diagnosis
• Auto re-start after power interruption
• PRE-CHARGED WITH REFRIGERANT for up to 30 metres pipe length
• Old pipework can be reused.
Technical Data
PKA-RP60FAL Indoor Unit
| Capacity (kW): |
|
| Heating (Nominal) (Low - High) |
7.00 (2.80 - 8.20) |
| Cooling (Nominal) (Low - High) |
6.00 (2.70 - 6.70) |
| Heating (UK) (Low - High) |
5.95 (2.40 - 6.95) |
| Cooling (UK) (Low - High) |
5.40 (2.45 - 6.05) |
| SHF R410A (Nominal) |
0.83 |
| COP / EER (Nominal) |
3.48 / 3.87 |
| Energy Label Heating / Cooling |
B / A |
| Width - mm |
1400 |
| Depth - mm |
235 |
| Height - mm |
340 |
| Weight - kg |
24 |
| Airflow (m3/min) - Lo-Hi |
15-20 |
| Noise (dBA) - Lo-Hi |
39-45 |
| Pipe Size Gas mm (in) |
15.88 (5/8) |
| Pipe Size Liquid mm (in) |
9.52 (3/8) |
| Electrical Supply |
Fed by Outdoor Unit |
| Phase |
Single |
| Fuse Rating (BS88) - HRC (A) |
6 |
| Interconnecting Cable No. Cores |
4 |
PUHZ-RP60VHA2 Outdoor Unit
| Width - mm |
950 |
| Depth - mm |
330 + 30 |
| Height - mm |
943 |
| Weight - kg |
75 |
| Noise (dBA) (Heating / Cooling) |
48 / 47 |
| Electrical Supply |
220-240v, 50Hz |
| Phase |
Single |
| Fuse Rating (BS88) - HRC (A) |
25 |
| System Power Input (kW) - Heating (Nominal) |
2.01 |
| System Power Input (kW) - Cooling (Nominal) |
1.55 |
| System Power Input (kW) - Heating (UK) |
1.79 |
| System Power Input (kW) - Cooling (UK) |
1.32 |
| Starting Current (A) |
5 |
| System Running Current (A) - Heating / Cooling |
7.93 / 7.04 |
| Mains Cable No. Cores |
3 |
| Max Pipe Length (m) |
50 |
| Max Height Difference (m) |
30 |
| Charge (kg) - 30m |
3.5 |
|